Power Factor Controller

Power Factor Controller

Model No.︰HY121

Brand Name︰LASTONE

Country of Origin︰China

Unit Price︰-

Minimum Order︰100 pc

Inquire Now

Product Description

compensatorSummary


     HY series power Factor compensated controller takes the high performance SCM as the basic hardware,is made by the special control program for ten years service expe rience,because the computer high speed calculation capacity and logic judge capacity is adopted,this controller can realize the intelligence really.


Function characteristic


1.AC sample technology is applid for.

2.Digital integral,filter wave,no sensitivity to harmonic wave.

3.Reactive power as the control physical quantity,high control precision,without cut in and cut off shocking.

4.The control parameter is operated by digital, it is convenient to use,the data cant be lost when power off.

5.Adopts the auto optimized control scheme, to reduce the cut in and cut off times,it an improve the system service life.

6.Strong anti-interference,it can resist the 2000V interference pulse from power supply direct inputting,it cant loss the data until the machines is dead,so it is reliable and stable to run.

7.The number can display the power factor of power net,reactive power,voltage, current(measured by once),control parameter.

8.It has two modes of manual running and automatic running,it is convenient to operate and adjust for user.

9.It can judge and indicate the state of over voltage and under voltage,with the function of rapid cutting off the capacitor group,preventing the capacitor running  under the over voltage.

10.It has the optional function of cut in and off shock closing(it is noted when user   orders).

11.It has the optional function of single group capacitor delays for 200s from cut off  time to cut in time,so it can have enough discharging time after the capacitor cutting off, and reduce the impaction to power net when the capacitor cuts in again (it is  noted when user orders).

12.The input resistance of sample signal is less than 0.05Ωit can be got from the  measuring loop.

13.It has the selection function of automation and manual.

14.The operation manual includes amounts of disposal methods of faults, user  can install and adjust conveniently according to it.


Technical parameter


1.Basic parameter:

    Rated voltage:AC 380V/AC220V±10%

    Rated current:AC 0-5A

    Rated frequency:50Hz±5%

2.Control parameter:

    Sensitivity:100mA

    COSφ PRESET:0.70-0.99;THE STEP IS 0.01;FACTORY PRESET:0.98

    Cut in and off state:1-250S

    Over voltage protection:380-500/230-260V;step:1V,return difference:6V;

    Under voltage protection;340/180V;return difference:6V

    CT variety:50/5A----4000/5A;step:1;factory preset;500/5A

    Capacitance volume:0-125Kvar;factory preset:each branch circuit is 10Kvar.

    Contact volume:each branch circuit is 380*5A/220*7A

3.Measuring accuracy:

    voltage:±1.0%

    current:±1.0%

    Power factor:±1.0%

    Reactive power:±2.0%